A Synopsis: Medicare and Medicaid Programs; Fire Safety Requirements for Certain Health Care Facilities; Amendment

On March 25, 2005, Federal Register (Vol. 70, No. 57, page 15229) was published containing an interim final rule with comment period entitled "Medicare and Medicaid Programs; Fire Safety Requirements for Certain Health Care Facilities; Amendment."

The effective date of this regulation is May 24, 2005. Surveying of facilities for compliance with this requirement is expected to begin on May 24, 2006 to allow time for providers to install the required battery powered smoke detectors and to review and/or make any changes to their facility's operating and fire plans.

Background
The Government Accountability Office (GAO) recommended the installation of smoke detectors to provide additional early warning of a fire occurring in a nursing home.

Regulation Requirements
This regulation requires, among other items, the installation of battery powered smoke detectors in resident rooms and commons areas in non-sprinklered Long Term Care (LTC) facilities.

All nursing homes that are not fully sprinklered are required to comply with the requirements of this regulation. A fully sprinklered nursing home is one that has all areas sprinklered in accordance with National Fire Protection Association (NFPA) 13 "Standard for the Installation of Sprinkler Systems" without the use of waivers or the Fire Safety Evaluation System (FSES).

Installation and Maintenance
The Centers for Medicare & Medicaid Services (CMS) expects that these battery powered smoke detectors will be installed, at a minimum, in all resident sleeping rooms and common areas such as dining rooms, activity rooms, meeting rooms where residents are located on a regular basis, and other areas in the facility where residents may gather together with other residents, visitors, and staff.
  1. Detectors shall be installed in accordance with the manufacturer's recommendations, but at a minimum, one shall be installed in each resident sleeping room.
  2. In larger rooms detectors shall be installed in accordance with the manufacturer's recommendations but not more than 30 feet apart.
  3. The detectors shall be tested weekly and batteries changed at least semi-annually, or, if the battery has a longer life in accordance with the manufacture's recommendations.
  4. Additional maintenance may be required such as cleaning on a regular basis, to ensure the detectors operate properly.
  5. CMS expects that facilities will keep records of all maintenance, testing and battery changing and have such records available at the time of any inspection.
Facility fire plans may need to be modified and staff trained in response to the alarm from a smoke detector. It is expected that the staff shall respond to an alarm sounding from one of these detectors by activating the facility wide fire alarm system without delay.

Survey Implications
Beginning on May 24, 2006 deficiencies concerning the installation and maintenance of these smoke detectors shall be cited on Life Safety Code (LSC) surveys using the LSC Form CMS-2786R at tag K-54 with a Scope/Severity level of D, E, or F depending on the particular situation. Documentation of the smoke detection system installation will be included in the remarks section of the Form CMS-2786R. A waiver of this requirement cannot be granted due to the negative impact on the health and safety of the residents of the facility. Emergency plan deficiencies concerning facility response to individual smoke detector activation will be cited at tag K-48 with a Scope/Severity level of D, E, or F depending on the particular situation.

Last Updated : 4/3/2006 3:08:38 PM

  Search


 AAHSA.org Web Site Map
 

  Quick Links
 


AAHSA Preferred Food Procurement Vendor

Entegra Procurement Services

Entegra provides procurement management services for food and related supplies, housekeeping, paper products, pest control, uniforms, linens. As an AAHSA preferred vendor, they offer special pricing to AAHSA's members.

Contact: Colleen Coady.
(215) 836-4573
www.entegraPS.com





American Association of Homes and Services for the Aging
2519 Connecticut Ave., NW, Washington, D.C. 20008
phone 202.783.2242, fax 202.783.2255